HVAC/R and refrigeration parts supplier in the UAE since 1983, with showrooms in Deira (Dubai), Industrial Area 6 (Sharjah) and Musaffah (Abu Dhabi). We stock compressors, condensing units, refrigerant gas, copper coil, controls, gauges, fan motors and tools for contractors, AC and cold-room technicians, supermarkets and industrial sites.


Thermostat Set Points, Differentials and Common Mistakes in UAE Conditions
Quick answer: Typical set points are 0 to 5 °C for chilled storage, -18 °C or below for frozen, and 22 to 25 °C for comfort AC. Set a differential of 2 to 4 K on cold rooms to avoid short cycling.
A good thermostat still fails if it is set badly. Here is how to set it right, especially in UAE heat.
What set points should you use?
Chilled food storage: 0 to 5 °C
Frozen storage: -18 °C or below
Comfort AC: 22 to 25 °C
UAE food storage rules commonly call for chilled food at 5 °C or colder and frozen food at -18 °C or colder. Always confirm with your municipality and the product’s own storage needs.
What is a differential?
The differential is the gap between the temperature where the compressor stops and where it restarts. Too small, and it starts too often. Too large, and the room swings too much. For cold rooms, 2 to 4 K is common.
Worked example: A dairy cold room needs 2 to 4 °C. Set the cut-out at 2 °C with a 2 K differential, and the compressor restarts at 4 °C. That keeps the room within range and below the 5 °C limit.
Why does UAE climate matter?
Heat: Frequent door openings and high ambient temperatures add load, so units cycle more. Keep the probe away from the door.
Dust and humidity: Choose a sealed enclosure, such as IP65, for wet or dusty areas.
Accuracy: Check readings against a reference thermometer twice a year.
Mistakes to avoid
Placing the sensor next to the evaporator or door.
Setting the differential too small, causing short cycling.
Switching a compressor directly through a relay that is too small.
Treating the thermostat as a safety device. It is a control, not a protection device.
FAQ
What set point should a cold room or freezer use? Chilled is typically 0 to 5 °C, frozen is -18 °C or below.
Unsure about your settings?
Get in touch with the Haste Trading team, who have supplied HVAC/R products in the UAE since 1983. Always confirm requirements against the equipment manual and local food safety rules.